Reading Registers
LiquidRanger Reading registers (read only) contain the measurement display value. Two registers are used
for the reading associated with each point.
Port 1 Reading registers range from 40121 to 40240, corresponding to the AiRanger IV points of measure.
Registers 40121 and 40122 apply to point 1, 40123 and 40124 to point 2, etc.
Check the first register for a value of 56,797 ($DDDD) (point out of service) or 61,166 ($EEEE) (display
overflow). For any other value, convert the register values to a floating point decimal (FPD) value by:
FPD = Register 1 (decimal equivalent) value +
Register 2 (decimal equivalent) value
10,000
The range of FPD values possible is 0.0 to 9,999.9999
Confidence Registers
LiquidRanger Confidence registers (read only) contain the echo confidence value of the associated point of
measure. Port 1 Confidence registers range from 40241 to 40300. Register 40241 corresponds to point 1,
40242 to point 2, etc.
Analog Registers
LiquidRanger Analog registers (read only) contain a value representing the LiquidRanger mA output for the
associated point of measure. Port 1 Analog registers range from 40301 to 40360. Register 40301
corresponds to point 1, 40302 to point 2, etc. The Analog register value range is 000 ($000) to 4095 ($FFF).
Divide the decimal equivalent by 204.75 to calculate the mA value.
Air Temperature Registers
LiquidRanger Air Temperature registers (read only) contain a value derived from the air temperature
measurement for the associated point of measure. Subtract 100 from the decimal equivalent of this value for
degrees Celcius. Port 1 Air Temperature registers range from 40361 to 40420. Register 40361 corresponds to
point 1 , 40362 to point 2 etc. The Air Temperature register value range is ($32) = 20 = -80°C to ($FA)= 250 =
150°C.
Liquid Temperature Registers
LiquidRanger Liquid Temperature registers (read only) contain a value derived from the liquid temperature
measurement for the associated point of measure. Subtract 100 from the decimal equivalent of this value for
degrees Celcius. Port 1 Liquid Temperature registers range from 40421 to 40480. Register 40421
corresponds to point 1 , 40422 to point 2 etc. The Liquid Temperature register value range is ($32) = 20 =
-80°C to ($FA) = 250 = 150°C.
LIQUIDRANGER WRITE ONLY REGISTERS
When a Port Initialization configures a BIC-II product port to suit a LiquidRanger, several write only registers
are established. Write the point of measure (1 to 60) number to the appropriate register.
NAME NUMBER DESCRIPTION
MT10 40481 scan the Port 1 specified point next
MT11 40482 acknowledge the Port 1 specified point alarm
MT12 40483 assign the Port 1 specified point to the priority scan loop
MT13 40484 remove the Port 1 specified point from the priority scan loop.
PL-371 9 – 12