AIRANGER XPL
When the BIC-II is in the AiRanger mode (factory setting), the AiRanger XPL, XPL Plus or DPL Plus
Measurement message (MT00) will be as follows:
Data ASCII Example
Field Character Description
SOM STX start of message
BIC-II I.D. 1 BIC-II #1 (e.g.) (range = 1 to 8)
MT 00 Message Type 00 (e.g.) (Product Data)
POINT 001 point #1 (e.g.) (range = 000 to 010), (000 to 003 for DPL Plus)
READING 2758 measurement value (e.g.) (range = 0000 to 9999, no decimal point)
STATUS A F not a priority point (e.g.) (E = priority point)
STATUS B 0 valid echo (e.g.) (3 = Fail-safe timer expired)
STATUS C 0 not in level alarm (e.g.)
(2 = Lo alarm)
(3 = Lo Lo alarm)
(4 = Hi alarm)
(C = Hi Hi alarm)
STATUS D 0 always the same as STATUS C
STATUS E 0 not in Band or Rate alarm (e.g.)
(2 = Rate alarm 1)
(3 = Rate alarm 2)
(8 = Band alarm 2)
(C = Band alarm 1)
STATUS F 0 no decimal point, no temp alarm, transducer’s OK. (e.g.)
(1 = decimal 1 digit from right)
(2 = decimal 2 digits from right)
(3 = decimal 3 digits from right)
(4 = Temp alarm, no decimal point)
(5 = Temp alarm, 1 decimal place)
(6 = Temp alarm, 2 decimal places)
(7 = Temp alarm, 3 decimal places)
(8 = defective transducer, no decimal point)
(9 = defective transducer, 1 decimal place)
(A = defective transducer, 2 decimal places)
(B = defective transducer, 3 decimal places)
(C = defective transducer, Temp alarm, no decimal point)
(D = defective transducer, Temp alarm, 1 decimal place)
(E = defective transducer, Temp alarm, 2 decimal places)
(F = defective transducer, Temp alarm, 3 decimal places)
CONFIDENCE 99 valid echo (e.g.) (00 = loss of echo)
ANALOG 000 always 000
EOM CR end of message
96/01/09
PL-371 7 – 7