MSG (Product Message)
Contains the message received from (or in some cases, transmitted to) the product connected to the BIC-II
product port.
The type and sequence of the data fields will be dependent upon the product type and the message type.
Refer to the appropriate product instruction manual for the message structure.
MT (Message Type)
Identifies the type of message received from (or in some cases, transmitted to) the product connected to the
BIC-II product port.
Refer to the appropriate product instruction manual for the list of message types available.
Message type 02 is a BIC-II generated message indicating the product "HOLD" condition has been removed.
TX (Number of Transmits)
Identifies the number of times each message will be transmitted from the BIC-II to the AiRanger IV or
LiquidRanger connected to the BIC-II product port.
ASCII values = 1 to 9
BAUD
Identifies the BIC-II/Product communication baud rate.
ASCII values = 00300
01200
02400
04800
09600
Refer to Functional \ Product Load Factor, prior to establishing values.
PARITY
Identifies the data bit parity that will be utilized in each byte (character) of the messages received from or
transmitted to the product connected.
ASCII values = E (even)
O (odd)
N (none)
DATA
Identifies the number of data bits in each byte received from (or transmitted to) the product connected to the
BIC-II product port.
ASCII values = 7
8
PL-371 8 – 4