P15 RATE OUTPUT AVERAGE
Defines the period in seconds between Rate Output updates. The value held, corresponds to the averaged
Rate of the previous period. Range = 0 to 999. A value of 0 may be entered if Rate output averaging is
not desired.
enter: desired value (F = 0)
P16 RATE BAR GRAPH ASSIGNMENT
Defines the output value the Rate Bar Graph Display represents, as a percent of span.
enter: 0 = Rate Output (P14) (F)
1 = undamped Rate
2 = Rate Display (P11)
P17 RATE OUTPUT MIN
Adjusts the Rate Output reference value for minimum material flowrate. Range = 0 to 4095.
a) With Change Mode activated and mA meter in series with the load connected to TB1-20,21.
b) Press "CLEAR" before keying in the estimated reference value, and pressing "ENTER".
c) Repeat step b) as required to produce the desired minimum Rate Output.
Briefly press "4" (increase by 10’s), or "8" (decrease by 1’s) to fine adjust the reference value, if necessary.
enter: 0 = no adjustment required
1 = Activate Change Mode (F = 631, for 4.00 mA)
P18 RATE OUTPUT MAX
Adjusts the Rate Output reference value for maximum material flowrate. Range = 0 to 4095.
a) With Change Mode activated and mA meter in series with the load connected to TB1-20,21.
b) Press "CLEAR" before keying in the estimated reference value, and pressing "ENTER".
c) Repeat step b) as required to produce the desired minimum Rate Output.
Briefly press "4" (increase by 10’s), or "8" (decrease by 1’s) to fine adjust the reference value, if necessary.
enter: 0 = no adjustment required
1 = Activate Change Mode (F = 3160, for 20.00 mA)
PL-367 7 – 5