PRE START UP CHECKS
After the CompuScale III has been properly installed and interconnected, the following checks should be
performed prior to connecting power:
» all cable connections are correct and secure.
» the proper voltage has been selected (J1 on the mother board).
» SW1 and SW2 have been set as required.
» the POWER switch is in the OFF position.
Connect power to TB1-51,52 and ground to TB1-50 of the CompuScale III. Ensure all connections are secure.
Do not operate the CompuScale III with the
ground (earth) wire disconnected.
INITIAL START UP
Set the CompuScale III POWER switch to the ON position. The CompuScale III will enter the following
initialization routine.
COMPUSCALE/FLO III (REV DATE) (EPROM 2 REV)
TEST : (MESSAGES)
PL-367 4 – 3